  • Safety switch with integrated evaluation electronics
  • No series connection
  • Short circuit monitoring
  • 2 safety outputs (semiconductor outputs)
  • Category 4/PL e according to EN ISO 13849-1
  • M12 plug connector 5-pin
  • Multicode
Approach direction Can be adjusted in 90° steps Short circuit monitoring The switch generates its own clock signal on the output cables OA/OB. Pay attention to this aspect when connecting to control systems and relays. Multicode evaluation Every suitable actuator is detected by the switch. Category according to EN 13849-1 Due to two redundantly designed semiconductor outputs (safety outputs) with internal monitoring suitable for:
  • Category 4 / PL e according to EN 13849-1
Important: To achieve the stated category in accordance with EN ISO 13849-1, both safety outputs (OA and OB) must be evaluated. LED indicator
STATEStatus LED
DIADiagnostics LED
Additional connections
DIADiagnostics output (semiconductor)
Typical operating distances With actuator CES-A-BBA and CES-A-BCA For a side approach direction for the actuator and safety switch, a minimum distance of s = 4 mm must be maintained so that the operating distance of the side lobes is not entered. With actuator CES-A-BPA For a side approach direction for the actuator and safety switch, a minimum distance of s = 6 mm must be maintained so that the operating distance of the side lobes is not entered. With actuator CES-A-BRN For a side approach direction for the actuator and safety switch, a minimum distance of s = 6 mm must be maintained so that the operating distance of the side lobes is not entered. Connector assignment
Plug connector (view of connection side) Pin Designation Function Conductor coloring of connection cable
1 UB Power supply, DC 24 V BN
2 OA Safety output, channel 1 GN
3 0V Ground, DC 0 V BU
4 OB Safety output, channel 2 YE
5 DIA Monitoring output GY
Housing material Plastic, PBT
Weight
Net 0,12 kg
Ambient temperature -20 ... 55 °C
Degree of protection IP67
Resilience to vibration In acc. with EN IEC 60947-5-2
Mounting distance min.40 mm
Installation orientation Any
Tightening torque
Fixing screws max.1 Nm
Ready delay 0,5 s
Switching frequency max.1 Hz
Connection M12 plug connector, 5-pin
Electrical connection ratings
Operating voltage DC
UB 24 V DC 15% ... 15% Reverse polarity protected, regulated, residual ripple < 5 %, PELV
Current consumption
No load on outputs max.50 mA
Fusing
External (operating voltage) 0,25 ... 8 A
Rated insulation voltage Ui 300 V
Rated impulse withstand voltage Uimp max.1,5 kV
EMC protection requirements In acc. with EN IEC 60947-5-3
Degree of contamination (external, according to EN 60947-1) 3
Switch-on time
Safety outputs max.400 ms
Safety class III
Risk time according to EN 60947-5-3 max.260 ms
Monitoring output DIA
Type of output p-switching, short circuit-proof
Switching current max.200 mA
Output voltage 0,8 x UB ... UB V DC
Safety outputs OA/OB
Test pulses max.0,4 ms
Type of output Semiconductor outputs, p-switching, short circuit-proof
Switching current
per safety output 1 ... 400 mA
Output voltage
LOW U(OA) / U(OB) 0 ... 1 V DC
HIGH U(OA) / U(OB) UB-1,5 ... UB V DC
Utilization category according to EN 60947-5-2
DC-13 24V 400mA
Rated conditional short-circuit current max.100 A
Off-state current Ir max.0,25 mA
Discrepancy time max.10 ms
Work area
Repeat accuracy R ?10
Other
For the approval according to UL the following applies Operation only with UL class 2 power supply, or equivalent measures
Reliability values according to EN ISO 13849-1
Monitoring of the safety guard position
Category 4
Performance Level PL e
PFHD 2.1 x 10-9
Mission time 20
In combination with Actuator CES-A-BDA-18-156935Operating distance
Switch-on distance 19 mm
Assured switch-off distance Sar max.45 mm
Assured operating distance Sao min.10 mm
Switching hysteresis min.1 mm
In combination with Actuator CES-A-BPAOperating distance
Switch-on distance 22 mm
Assured switch-off distance Sar max.58 mm
Assured operating distance Sao min.18 mm
Switching hysteresis min.1 mm
In combination with Actuator CES-A-BRN-100251Operating distance
Switch-on distance 27 mm
Assured switch-off distance Sar max.75 mm
Assured operating distance Sao min.20 mm
Switching hysteresis 3 mm
In combination with Actuator CES-A-BBAOperating distance
Switch-on distance 18 mm
Assured switch-off distance Sar max.45 mm
Assured operating distance Sao min.15 mm
Switching hysteresis min.1 mm
''